Description
The HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime generates predictable authentication tokens for cookies, which makes it easier for remote attackers to bypass authentication via a crafted cookie.
Source
cret@cert.org
NVD status
Analyzed

Social media

Hype score
Not currently trending

Risk scores

CVSS 2.0

Type
Primary
Base score
9.3
Impact score
10
Exploitability score
8.6
Vector string
AV:N/AC:M/Au:N/C:C/I:C/A:C

Weaknesses

nvd@nist.gov
CWE-287