CVE-2013-2806

Published Mar 26, 2019

Last updated 5 years ago

Overview

Description
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “End of Current Record” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size.” Then the service will calculate an incorrect value for the “End of Current Record” field causing access violations that lead to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation security advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
Source
ics-cert@hq.dhs.gov
NVD status
Modified

Risk scores

CVSS 3.0

Type
Primary
Base score
7.5
Impact score
3.6
Exploitability score
3.9
Vector string
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Severity
HIGH

CVSS 2.0

Type
Primary
Base score
7.8
Impact score
6.9
Exploitability score
10
Vector string
AV:N/AC:L/Au:N/C:N/I:N/A:C

Weaknesses

nvd@nist.gov
CWE-190
ics-cert@hq.dhs.gov
CWE-190

Social media

Hype score
Not currently trending

Configurations