CVE-2013-2807

Published Mar 26, 2019

Last updated 5 years ago

Overview

Description
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “Total Record Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size” that will cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
Source
ics-cert@hq.dhs.gov
NVD status
Modified

Risk scores

CVSS 3.0

Type
Primary
Base score
7.5
Impact score
3.6
Exploitability score
3.9
Vector string
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Severity
HIGH

CVSS 2.0

Type
Primary
Base score
7.8
Impact score
6.9
Exploitability score
10
Vector string
AV:N/AC:L/Au:N/C:N/I:N/A:C

Weaknesses

nvd@nist.gov
CWE-125
ics-cert@hq.dhs.gov
CWE-190

Social media

Hype score
Not currently trending

Configurations