CVE-2016-7112
Published Sep 6, 2016
Last updated 7 years ago
Overview
- Description
- A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Attackers with network access to the device's web interface (port 80/tcp) could possibly circumvent authentication and perform certain administrative operations.
- Source
- cve@mitre.org
- NVD status
- Modified
Social media
- Hype score
- Not currently trending
Risk scores
CVSS 3.0
- Type
- Primary
- Base score
- 9.8
- Impact score
- 5.9
- Exploitability score
- 3.9
- Vector string
- CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
- Severity
- CRITICAL
CVSS 2.0
- Type
- Primary
- Base score
- 10
- Impact score
- 10
- Exploitability score
- 10
- Vector string
- AV:N/AC:L/Au:N/C:C/I:C/A:C
Weaknesses
- nvd@nist.gov
- CWE-287
Configurations
[ { "nodes": [ { "negate": false, "cpeMatch": [ { "criteria": "cpe:2.3:a:siemens:en100_ethernet_module_firmware:*:*:*:*:*:*:*:*", "vulnerable": true, "matchCriteriaId": "E452C818-6183-48B7-AC0C-05C605FAFCD8", "versionEndIncluding": "4.28" } ], "operator": "OR" }, { "negate": false, "cpeMatch": [ { "criteria": "cpe:2.3:h:siemens:en100_ethernet_module:-:*:*:*:*:*:*:*", "vulnerable": false, "matchCriteriaId": "DAC429FD-7148-4A68-AA81-8FBADA588F4E" } ], "operator": "OR" } ], "operator": "AND" } ]