Overview
- Description
- An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Description: The filetype 0x03 allows users write access, allowing the ability to overwrite the Master Password value stored in the file.
- Source
- talos-cna@cisco.com
- NVD status
- Analyzed
Risk scores
CVSS 3.1
- Type
- Primary
- Base score
- 9.8
- Impact score
- 5.9
- Exploitability score
- 3.9
- Vector string
- CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
- Severity
- CRITICAL
CVSS 3.0
- Type
- Secondary
- Base score
- 10
- Impact score
- 6
- Exploitability score
- 3.9
- Vector string
- CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
- Severity
- CRITICAL
CVSS 2.0
- Type
- Primary
- Base score
- 7.5
- Impact score
- 6.4
- Exploitability score
- 10
- Vector string
- AV:N/AC:L/Au:N/C:P/I:P/A:P
Weaknesses
- nvd@nist.gov
- NVD-CWE-noinfo
Social media
- Hype score
- Not currently trending
Configurations
[ { "nodes": [ { "negate": false, "cpeMatch": [ { "criteria": "cpe:2.3:o:rockwellautomation:micrologix_1400_b_firmware:*:*:*:*:*:*:*:*", "vulnerable": true, "matchCriteriaId": "E3CFD00A-A73C-46AA-B6BD-93C44FBCC98F", "versionEndIncluding": "21.2" } ], "operator": "OR" }, { "negate": false, "cpeMatch": [ { "criteria": "cpe:2.3:h:rockwellautomation:micrologix_1400:-:*:*:*:*:*:*:*", "vulnerable": false, "matchCriteriaId": "196EA0BE-FDF3-46BE-B3DA-5F49208C5D80" } ], "operator": "OR" } ], "operator": "AND" } ]