CVE-2017-7575
Published Apr 6, 2017
Last updated 8 years ago
Overview
- Description
- Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus port (502/tcp). Subsequently the application may be arbitrarily downloaded, modified, and uploaded.
- Source
- cve@mitre.org
- NVD status
- Modified
Social media
- Hype score
- Not currently trending
Risk scores
CVSS 3.0
- Type
- Primary
- Base score
- 9.8
- Impact score
- 5.9
- Exploitability score
- 3.9
- Vector string
- CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
- Severity
- CRITICAL
CVSS 2.0
- Type
- Primary
- Base score
- 5
- Impact score
- 2.9
- Exploitability score
- 10
- Vector string
- AV:N/AC:L/Au:N/C:P/I:N/A:N
Weaknesses
- nvd@nist.gov
- CWE-200
Configurations
[ { "nodes": [ { "negate": false, "cpeMatch": [ { "criteria": "cpe:2.3:o:schneider-electric:modicon_tm221ce16r_firmware:1.3.3.3:*:*:*:*:*:*:*", "vulnerable": true, "matchCriteriaId": "26C40BAF-2C91-4069-A62E-1B1E60BA1619" } ], "operator": "OR" }, { "negate": false, "cpeMatch": [ { "criteria": "cpe:2.3:h:schneider-electric:modicon_tm221ce16r:-:*:*:*:*:*:*:*", "vulnerable": false, "matchCriteriaId": "00715571-AC4B-4B1F-8E65-385B56F2004C" } ], "operator": "OR" } ], "operator": "AND" } ]