- Description
- In ABB SREA-01 revisions A, B, C: application versions up to 3.31.5, and SREA-50 revision A: application versions up to 3.32.8, an attacker may access internal files of ABB SREA-01 and SREA-50 legacy remote monitoring tools without any authorization over the network using a HTTP request which refers to files using ../../ relative paths. Once the internal password file is retrieved, the password hash can be identified using a brute force attack. There is also an exploit allowing running of commands after authorization.
- Source
- ics-cert@hq.dhs.gov
- NVD status
- Modified
CVSS 3.0
- Type
- Primary
- Base score
- 9.8
- Impact score
- 5.9
- Exploitability score
- 3.9
- Vector string
- CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
- Severity
- CRITICAL
CVSS 2.0
- Type
- Primary
- Base score
- 5
- Impact score
- 2.9
- Exploitability score
- 10
- Vector string
- AV:N/AC:L/Au:N/C:P/I:N/A:N
- Hype score
- Not currently trending
[
{
"nodes": [
{
"negate": false,
"cpeMatch": [
{
"criteria": "cpe:2.3:o:abb:srea-50_firmware:*:*:*:*:*:*:*:*",
"vulnerable": true,
"matchCriteriaId": "1DF23E98-6E25-4D94-925E-E836C7D706B4",
"versionEndIncluding": "3.32.8"
}
],
"operator": "OR"
},
{
"negate": false,
"cpeMatch": [
{
"criteria": "cpe:2.3:h:abb:srea-50:-:*:*:*:*:*:*:*",
"vulnerable": false,
"matchCriteriaId": "52210FA9-8C19-4717-9C1E-CD2ADF4BD540"
}
],
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"negate": false,
"cpeMatch": [
{
"criteria": "cpe:2.3:o:abb:srea-01_firmware:*:*:*:*:*:*:*:*",
"vulnerable": true,
"matchCriteriaId": "4EF6D274-B243-4246-802C-8A90DF57176A",
"versionEndIncluding": "3.31.5"
}
],
"operator": "OR"
},
{
"negate": false,
"cpeMatch": [
{
"criteria": "cpe:2.3:h:abb:srea-01:-:*:*:*:*:*:*:*",
"vulnerable": false,
"matchCriteriaId": "A677B3B0-7EAF-44AE-B75E-119E8EB72496"
}
],
"operator": "OR"
}
],
"operator": "AND"
}
]