CVE-2018-13805

Published Oct 10, 2018

Last updated 4 days ago

Overview

Description
A vulnerability has been identified in SIMATIC ET 200SP Open Controller (All versions >= V2.0 and < V2.1.6), SIMATIC S7-1500 Software Controller (All versions >= V2.0 and < V2.5), SIMATIC S7-1500 incl. F (All versions >= V2.0 and < V2.5). An attacker can cause a denial-of-service condition on the network stack by sending a large number of specially crafted packets to the PLC. The PLC will lose its ability to communicate over the network. This vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no privileges and no user interaction. An attacker could use this vulnerability to compromise availability of the network connectivity. At the time of advisory publication no public exploitation of this vulnerability was known.
Source
productcert@siemens.com
NVD status
Modified

Risk scores

CVSS 3.0

Type
Primary
Base score
7.5
Impact score
3.6
Exploitability score
3.9
Vector string
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Severity
HIGH

CVSS 2.0

Type
Primary
Base score
5
Impact score
2.9
Exploitability score
10
Vector string
AV:N/AC:L/Au:N/C:N/I:N/A:P

Weaknesses

nvd@nist.gov
CWE-400

Social media

Hype score
Not currently trending

Configurations