CVE-2019-13927

Published Dec 12, 2019

Last updated 5 years ago

Overview

Description
A vulnerability has been identified in Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 (All firmware versions < V6.00.320), Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 (All firmware versions < V6.00.320), Desigo PX automation controllers PXC22.1-E.D, PXC36-E.D, PXC36.1-E.D with activated web server (All firmware versions < V6.00.320). The device contains a vulnerability that could allow an attacker to cause a denial of service condition on the device's web server by sending a specially crafted HTTP message to the web server port (tcp/80). The security vulnerability could be exploited by an attacker with network access to an affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the device's web service. While the device itself stays operational, the web server responds with HTTP status code 404 (Not found) to any further request. A reboot is required to recover the web interface. At the time of advisory publication no public exploitation of this security vulnerability was known.
Source
productcert@siemens.com
NVD status
Analyzed

Risk scores

CVSS 3.1

Type
Primary
Base score
5.3
Impact score
1.4
Exploitability score
3.9
Vector string
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L
Severity
MEDIUM

CVSS 2.0

Type
Primary
Base score
5
Impact score
2.9
Exploitability score
10
Vector string
AV:N/AC:L/Au:N/C:N/I:N/A:P

Weaknesses

nvd@nist.gov
CWE-668
productcert@siemens.com
CWE-472

Social media

Hype score
Not currently trending

Configurations