CVE-2019-6572

Published May 14, 2019

Last updated 4 years ago

Overview

Description
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The affected device offered SNMP read and write capacities with a publicly know hardcoded community string. The security vulnerability could be exploited by an attacker with network access to the affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
Source
productcert@siemens.com
NVD status
Analyzed

Social media

Hype score
Not currently trending

Risk scores

CVSS 3.1

Type
Primary
Base score
9.1
Impact score
5.2
Exploitability score
3.9
Vector string
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N
Severity
CRITICAL

CVSS 2.0

Type
Primary
Base score
6.4
Impact score
4.9
Exploitability score
10
Vector string
AV:N/AC:L/Au:N/C:P/I:P/A:N

Weaknesses

nvd@nist.gov
CWE-798
productcert@siemens.com
CWE-200

Configurations