CVE-2020-11639

Published Jul 23, 2024

Last updated 4 months ago

Overview

Description
An attacker could exploit the vulnerability by injecting garbage data or specially crafted data. Depending on the data injected each process might be affected differently. The process could crash or cause communication issues on the affected node, effectively causing a denial-of-service attack. The attacker could tamper with the data transmitted, causing the product to store wrong information or act on wrong data or display wrong information. This issue affects Advant MOD 300 AdvaBuild: from 3.0 through 3.7 SP2. For an attack to be successful, the attacker must have local access to a node in the system and be able to start a specially crafted application that disrupts the communication. An attacker who successfully exploited the vulnerability would be able to manipulate the data in such way as allowing reads and writes to the controllers or cause Windows processes in 800xA for MOD 300 and AdvaBuild to crash.
Source
cybersecurity@ch.abb.com
NVD status
Awaiting Analysis

Risk scores

CVSS 3.1

Type
Secondary
Base score
7.8
Impact score
5.9
Exploitability score
1.8
Vector string
CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
Severity
HIGH

Weaknesses

cybersecurity@ch.abb.com
CWE-924

Social media

Hype score
Not currently trending