Overview
- Description
- Incorrect Access Control in Beckhoff Automation GmbH & Co. KG CX9020 with firmware version CX9020_CB3011_WEC7_HPS_v602_TC31_B4016.6 allows remote attackers to bypass authentication via the "CE Remote Display Tool" as it does not close the incoming connection on the Windows CE side if the credentials are incorrect.
- Source
- cve@mitre.org
- NVD status
- Analyzed
Risk scores
CVSS 3.1
- Type
- Primary
- Base score
- 9.8
- Impact score
- 5.9
- Exploitability score
- 3.9
- Vector string
- CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
- Severity
- CRITICAL
CVSS 2.0
- Type
- Primary
- Base score
- 7.5
- Impact score
- 6.4
- Exploitability score
- 10
- Vector string
- AV:N/AC:L/Au:N/C:P/I:P/A:P
Weaknesses
- nvd@nist.gov
- NVD-CWE-Other
Social media
- Hype score
- Not currently trending
Configurations
[ { "nodes": [ { "negate": false, "cpeMatch": [ { "criteria": "cpe:2.3:h:beckhoff:cx9020:6.02:build_4016.6:*:*:*:*:*:*", "vulnerable": true, "matchCriteriaId": "D1A3291C-B38B-4EBC-9D16-1979B5723FF2" } ], "operator": "OR" } ] } ]