- Description
- Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).
- Source
- cybersecurity@hitachienergy.com
- NVD status
- Modified
CVSS 3.1
- Type
- Primary
- Base score
- 7.5
- Impact score
- 3.6
- Exploitability score
- 3.9
- Vector string
- CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
- Severity
- HIGH
CVSS 2.0
- Type
- Primary
- Base score
- 7.1
- Impact score
- 6.9
- Exploitability score
- 8.6
- Vector string
- AV:N/AC:M/Au:N/C:N/I:N/A:C
- Hype score
- Not currently trending
[
{
"nodes": [
{
"negate": false,
"cpeMatch": [
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:12.0:*:*:*:*:*:*:*",
"vulnerable": true,
"matchCriteriaId": "9BA3F33A-8787-4128-A790-685BCB272A82"
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:12.2:*:*:*:*:*:*:*",
"vulnerable": true,
"matchCriteriaId": "FCD4343D-4B6E-4D6A-A2F3-EFA5CFE4290D"
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:12.4:*:*:*:*:*:*:*",
"vulnerable": true,
"matchCriteriaId": "9CCC7155-16F2-4E60-ABCB-0E6FF71CEC67"
}
],
"operator": "OR"
},
{
"negate": false,
"cpeMatch": [
{
"criteria": "cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:*",
"vulnerable": false,
"matchCriteriaId": "DE94252D-03EE-451B-8322-B4DBC790C6E9"
}
],
"operator": "OR"
}
],
"operator": "AND"
}
]