- Description
- Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP system. By default, ICCP is not configured and not enabled. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10.2 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*
- Source
- cybersecurity@hitachienergy.com
- NVD status
- Modified
Risk scores
CVSS 3.1
- Type
- Primary
- Base score
- 7.5
- Impact score
- 3.6
- Exploitability score
- 3.9
- Vector string
- CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
- Severity
- HIGH
Social media
- Hype score
- Not currently trending
Configurations
[ { "nodes": [ { "negate": false, "cpeMatch": [ { "criteria": "cpe:2.3:a:hitachienergy:microscada_x_sys600:*:*:*:*:*:*:*:*", "vulnerable": true, "matchCriteriaId": "6D017E2F-F8D8-4755-881A-53415CBC27EE", "versionEndIncluding": "10.3.1", "versionStartIncluding": "10.2" } ], "operator": "OR" }, { "negate": false, "cpeMatch": [ { "criteria": "cpe:2.3:h:hitachienergy:sys600:-:*:*:*:*:*:*:*", "vulnerable": false, "matchCriteriaId": "42B6499F-D82D-4B02-BBEC-60B36FB0C678" } ], "operator": "OR" } ], "operator": "AND" } ]