CVE-2022-31205

Published Jul 26, 2022

Last updated a year ago

Overview

Description
In Omron CS series, CJ series, and CP series PLCs through 2022-05-18, the password for access to the Web UI is stored in memory area D1449...D1452 and can be read out using the Omron FINS protocol without any further authentication.
Source
cve@mitre.org
NVD status
Analyzed

Risk scores

CVSS 3.1

Type
Primary
Base score
7.5
Impact score
3.6
Exploitability score
3.9
Vector string
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
Severity
HIGH

Weaknesses

nvd@nist.gov
CWE-312

Social media

Hype score
Not currently trending

Configurations