CVE-2022-33174

Published Jun 13, 2022

Last updated 2 years ago

Overview

Description
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
Source
cve@mitre.org
NVD status
Analyzed

Risk scores

CVSS 3.1

Type
Primary
Base score
7.5
Impact score
3.6
Exploitability score
3.9
Vector string
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
Severity
HIGH

CVSS 2.0

Type
Primary
Base score
5
Impact score
2.9
Exploitability score
10
Vector string
AV:N/AC:L/Au:N/C:P/I:N/A:N

Weaknesses

nvd@nist.gov
CWE-863

Social media

Hype score
Not currently trending

Configurations