CVE-2023-0052

Published Jan 20, 2023

Last updated a year ago

Overview

Description
SAUTER Controls Nova 200–220 Series with firmware version 3.3-006 and prior and BACnetstac version 4.2.1 and prior allows the execution of commands without credentials. As Telnet and file transfer protocol (FTP) are the only protocols available for device management, an unauthorized user could access the system and modify the device configuration, which could result in the unauthorized user executing unrestricted malicious commands.
Source
ics-cert@hq.dhs.gov
NVD status
Analyzed

Social media

Hype score
Not currently trending

Risk scores

CVSS 3.1

Type
Primary
Base score
8.8
Impact score
5.9
Exploitability score
2.8
Vector string
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
Severity
HIGH

Weaknesses

nvd@nist.gov
CWE-306
ics-cert@hq.dhs.gov
CWE-306

Configurations