CVE-2023-38121

Published May 3, 2024

Last updated 6 months ago

Overview

Description
Inductive Automation Ignition OPC UA Quick Client Cross-Site Scripting Remote Code Execution Vulnerability. This vulnerability allows remote attackers to execute arbitrary code on affected installations of Inductive Automation Ignition. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file. The specific flaw exists within the handling of the id parameter provided to the Inductive Automation Ignition web interface. The issue results from the lack of proper validation of user-supplied data, which can lead to the injection of an arbitrary script. An attacker can leverage this vulnerability to execute arbitrary code in the context of SYSTEM. Was ZDI-CAN-20355.
Source
zdi-disclosures@trendmicro.com
NVD status
Awaiting Analysis

Risk scores

CVSS 3.0

Type
Secondary
Base score
8.3
Impact score
6
Exploitability score
1.6
Vector string
CVSS:3.0/AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H
Severity
HIGH

Weaknesses

zdi-disclosures@trendmicro.com
CWE-79

Social media

Hype score
Not currently trending