Description
Triangle MicroWorks SCADA Data Gateway Trusted Certification Unrestricted Upload of File Remote Code Execution Vulnerability. This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed. The specific flaw exists within the trusted certification feature. The issue lies in the handling of the OpcUaSecurityCertificateAuthorityTrustDir variable, which allows an arbitrary file write with attacker-controlled data. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-20537.
Source
zdi-disclosures@trendmicro.com
NVD status
Awaiting Analysis

Risk scores

CVSS 3.0

Type
Secondary
Base score
7.2
Impact score
5.9
Exploitability score
1.2
Vector string
CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H