- Description
- Improper Authentication vulnerability in the mobile monitoring feature of ICONICS GENESIS64 versions 10.97 to 10.97.2, Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.2 and Mitsubishi Electric MC Works64 all versions allows a remote unauthenticated attacker to bypass proper authentication and log in to the system when all of the following conditions are met: * Active Directory is used in the security setting. * “Automatic log in” option is enabled in the security setting. * The IcoAnyGlass IIS Application Pool is running under an Active Directory Domain Account. * The IcoAnyGlass IIS Application Pool account is included in GENESIS64TM and MC Works64 Security and has permission to log in.
- Source
- Mitsubishielectric.Psirt@yd.MitsubishiElectric.co.jp
- NVD status
- Awaiting Analysis
Risk scores
CVSS 3.1
- Type
- Secondary
- Base score
- 5.9
- Impact score
- 3.6
- Exploitability score
- 2.2
- Vector string
- CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N
- Severity
- MEDIUM
Weaknesses
- Mitsubishielectric.Psirt@yd.MitsubishiElectric.co.jp
- CWE-287